Grid Prep Start free Buy US$10

Topic guide · NERC System Operator Certification

Three-part communication and COM-002-4

COM-002-4 sets the rules for issuing and receiving an Operating Instruction: issue, repeat back, confirm. This is what it asks of each side, in normal operations and in an Emergency, and where the exam tests it.

The terms the standard leans on

COM-002-4 leans on two terms from the Glossary of Terms Used in NERC Reliability Standards.

Operating Instruction. A command from operating personnel responsible for the Real-time operation of the interconnected Bulk Electric System (BES) to change or preserve the state, status, output or input of a BES Element or Facility. A discussion of general information, or of options for resolving an operating concern, is not a command, so it is not an Operating Instruction.

Emergency (entered as "Emergency or BES Emergency"). Any abnormal system condition that needs automatic or immediate manual action to prevent or limit a failure of transmission facilities or generation supply that could harm BES reliability. R5 to R7 apply only during one.

Three-part communication is not a Glossary term, and COM-002-4 never uses the phrase. NERC uses it as a label: the content outlines name it as an example under knowledge area 6.b, and the Program Manual lists it among recognized operator training topics. The three parts come from the standard's rules for an oral two-party, person-to-person Operating Instruction: the issuer gives it, the receiver repeats it back, the issuer confirms the repeat.

Who it applies to

COM-002-4 applies to five functional entities: the Balancing Authority (BA), Reliability Coordinator (RC), Transmission Operator (TOP), Generator Operator (GOP) and Distribution Provider (DP).

RequirementApplies to
R1 documented protocols, R2 training, R4 yearly assessmentBA, RC, TOP
R3 training for receiversDP, GOP
R5 issuing during an EmergencyBA, RC, TOP
R6 receiving during an EmergencyBA, DP, GOP, TOP
R7 burst instructions during an EmergencyBA, RC, TOP

The GOP and DP have no protocol duty of their own: they train their receivers and, during an Emergency, repeat back or ask for a reissue. R6 does not list the RC.

COM-002-4 has been in force since July 1, 2016. On November 6, 2026 its nerc.com page showed it as mandatory and subject to enforcement, with no later version listed. Which desk needs which certificate: which NERC certification you need.

The documented protocol (R1)

Each BA, RC and TOP must write communications protocols for its operating personnel who issue and receive Operating Instructions. At a minimum, the protocols must:

  1. Require English for oral and written Operating Instructions unless the parties agree otherwise. Another language may be used for internal operations (Part 1.1).
  2. Require the issuer of an oral two-party, person-to-person instruction to confirm a correct repeat, reissue the instruction if the repeat is wrong or the receiver asks, or take an alternative action if no response comes or it was not understood (Part 1.2).
  3. Require the receiver to repeat the instruction, "not necessarily verbatim", and get the issuer's confirmation that the repeat was correct, or else ask the issuer to reissue it (Part 1.3).
  4. Require the issuer of a written or oral burst instruction, sent by a single party to multiple parties, to confirm or verify that at least one receiver got it (Part 1.4).
  5. Specify when an instruction needs time identification, and the format for it (Part 1.5).
  6. Specify the names to use for Transmission interface Elements and Transmission interface Facilities (Part 1.6).

Training and the yearly check (R2 to R4)

The BA, RC and TOP must train each operator responsible for the Real-time operation of the interconnected BES on the protocols before that operator issues an Operating Instruction (R2). The GOP and DP must train each person who can receive an oral two-party, person-to-person instruction before that person receives one: repeat it back and get confirmation, or ask for a reissue (R3). Both are initial training.

At least once every 12 calendar months, the BA, RC and TOP must assess its operators' adherence to the protocols, give them feedback and take corrective action where it judges that appropriate, and assess whether the protocols are effective, changing them as needed (R4).

During an Emergency (R5 to R7)

R5 to R7 make the actions of Parts 1.2 to 1.4 direct requirements while an Emergency is under way, each with a High violation risk factor.

The issuer. A BA, RC or TOP issuing an oral two-party, person-to-person Operating Instruction must confirm a correct repeat, reissue the instruction if the repeat is wrong or the receiver asks, or take an alternative action if no response comes or it was not understood (R5).

The receiver. A BA, DP, GOP or TOP that receives one must repeat it, not necessarily word for word, and get the issuer's confirmation, or ask the issuer to reissue it (R6).

Burst instructions. A BA, RC or TOP issuing a written or oral single-party to multiple-party burst instruction must confirm or verify that at least one receiver got it (R7). R5 and R6 exclude burst instructions, so a burst needs no repeat-back from each receiver.

Evidence can include dated, time-stamped voice recordings and dated operator logs (M5 to M7). Voice recordings are kept at least 90 calendar days, other evidence for the current and previous calendar year. A miss under R5, R6 or R7 reaches the Severe violation severity level when instability, uncontrolled separation or cascading failures result.

Where the exam tests it

Communications and Data is 12 scored questions on all four exams. Within it, knowledge area 6.b, Communication Methods, carries 3: 3 of the 120 scored on RC and BT, and 3 of the 100 on TO and BI. The outline gives three-part communication and RCIS as that area's examples, so not every 6.b question is about COM-002-4. All four outlines also list communicating effectively, accurately and concisely with other parties among the operator's tasks. The pass mark is a count of correct answers, not a percentage: see the passing score.

Question 1 · Recall6.b Communication Methods (e.g. Three-Part Communication, RCIS)

At least once every twelve calendar months, what must a Transmission Operator do about its documented communications protocols?

  1. A. Retrain every operator on the protocols and record the attendance
  2. B. File the protocols and the training records with its Reliability Coordinator
  3. C. Assess operator adherence and protocol effectiveness, and act on each
  4. D. Run a drill on the protocols with each Generator Operator in its area
Show the answer

Answer C Assess operator adherence and protocol effectiveness, and act on each

Requirement R4 sets a twelve-calendar-month cycle with two halves: assess adherence by the operators who issue and receive Operating Instructions, give them feedback and take corrective action as the entity deems appropriate, and assess whether the protocols themselves are effective, modifying them as necessary. Training under Requirement R2 is initial training, not an annual event.

Reference: COM-002-4 R4

From COM-002-4 and its standard page, the Glossary of Terms, the four content outlines (June 2023) and the Program Manual (V4.2, and V4.3 as posted in October 2026, which lists the same topic), as posted on nerc.com in October and November 2026.

Questions

Three-part communication FAQ

Is three-part communication defined in the NERC Glossary?

No. The Glossary defines Operating Instruction and Emergency, and COM-002-4 sets out the steps without using the phrase. The three parts are issue, repeat back and confirm.

Does the receiver have to repeat the instruction word for word?

No. COM-002-4 says the repeat need not be verbatim. The receiver must then get the issuer's confirmation that it was correct, or ask for the instruction to be reissued.

Is a discussion of options an Operating Instruction?

No. The Glossary says that talking through general information, or possible ways to resolve an operating concern, is not a command. An Operating Instruction is a command to change or preserve the state of a BES Element or Facility.

Do the repeat-back rules apply outside an Emergency?

Yes, through the BA's, RC's or TOP's documented protocol under R1, whose adherence is assessed every 12 calendar months under R4. R5 to R7 add direct requirements that apply only during an Emergency.

What does the issuer of a burst instruction have to do?

Confirm or verify that at least one receiver got it. Each receiver does not have to repeat it back.

Free to start

Practice the communications questions

Grid Prep is free to start: 50 practice answers and a 30-question timed taster, sampled to your exam's outline. Full Access is US$10 once on the web.