What Reporting ACE is
NERC's Glossary defines Area Control Error as the instantaneous difference between an entity's actual and scheduled net interchange, allowing for Frequency Bias, meter error and, where used, inadvertent interchange management. Compliance uses Reporting ACE: its scan-rate values for a Balancing Authority Area, in MW, given as:
Reporting ACE = (NIA − NIS) − 10B (FA − FS) − IME + IIM
- NIA, Actual Net Interchange: the algebraic sum of actual MW flows on all Tie Lines and Pseudo-Ties with adjacent Balancing Authority Areas in the same Interconnection, leaving out asynchronous DC ties to another Interconnection.
- NIS, Scheduled Net Interchange: the algebraic sum of scheduled MW transfers with the same neighbors, including Dynamic Schedules and scheduled ramps.
- B, Frequency Bias Setting: a negative number, fixed or variable, in MW/0.1 Hz. It accounts for the Balancing Authority's Frequency Response and discourages withdrawal of that response through secondary control. The 10 converts it to MW/Hz.
- FA, Actual Frequency, the measured Interconnection frequency, and FS, Scheduled Frequency, 60.00 Hz except during a Time Error Correction.
- IME, Interchange Meter Error: corrects for data or equipment errors in the other terms.
- IIM, Inadvertent Interchange Management: null unless a regional procedure exists. In the Western Interconnection it is IATEC, Automatic Time Error Correction, which pays back Primary Inadvertent Interchange and corrects Time Error. ATEC applies only in the West, under its own WECC standard, BAL-004-WECC-4.
A worked number
Take an Eastern Interconnection Balancing Authority with these inputs: NIA = 520 MW, NIS = 500 MW, B = −50 MW/0.1 Hz, FA = 59.98 Hz, FS = 60.00 Hz, IME = 0, IIM null.
- Interchange term: 520 − 500 = 20 MW.
- Bias term: 10 × (−50) = −500 MW/Hz, and FA − FS = −0.02 Hz. −500 × (−0.02) = +10 MW, which the equation subtracts.
- Reporting ACE = 20 − 10 − 0 = 10 MW.
With frequency high by the same 0.02 Hz, the bias term flips sign and Reporting ACE is 20 + 10 = 30 MW. Because B is negative, −10B (FA − FS) has the same sign as the frequency error: low frequency lowers Reporting ACE, high frequency raises it.
What BAL-001-2 asks
BAL-001-2, Real Power Balancing Control Performance, exists to keep Interconnection frequency within defined limits. On November 6, 2026, nerc.com listed it as Mandatory Subject to Enforcement, effective July 1, 2016, with no later BAL-001 version.
It applies to Balancing Authorities and to Regulation Reserve Sharing Groups. A Balancing Authority that receives Overlap Regulation Service is not evaluated on CPS1 or the BAAL, and a member of a Regulation Reserve Sharing Group is the responsible entity only while it is not in active status in the group. Section E lists no regional variances.
R1: CPS1 over a rolling 12 months
The Balancing Authority, or the Regulation Reserve Sharing Group, must keep Control Performance Standard 1 at or above 100 percent for each preceding 12 consecutive calendar months, evaluated monthly. Attachment 1 gives CPS1 = (2 − CF) × 100%, so 100 percent or more means a compliance factor (CF) of 1.0 or less. CF is built from clock-minute averages of Reporting ACE, Frequency Error and the Frequency Bias Setting, divided by the square of the Interconnection's frequency bound, ε1: 0.018 Hz in the East, 0.0228 Hz in the West, 0.030 Hz in ERCOT and 0.021 Hz in Quebec.
R2: the BAAL and its clock-minute test
Each Balancing Authority's clock-minute average of Reporting ACE must not exceed its clock-minute Balancing Authority ACE Limit (BAAL) for more than 30 consecutive clock-minutes. Attachment 2 sets one limit at a time: with frequency on schedule neither applies, with frequency low only BAAL Low applies, and with frequency high only BAAL High. The trigger limits are FS ± 3ε1, so 59.946 Hz and 60.054 Hz in the East when FS is 60.00 Hz.
For the Balancing Authority above, BAAL Low = (−10B × (FTL Low − FS)) × (FTL Low − FS) / (FA − FS):
- FTL Low − FS = 59.946 − 60.000 = −0.054 Hz.
- −10B × (−0.054) = 500 × (−0.054) = −27 MW.
- (−0.054) / (−0.02) = 2.7, and −27 × 2.7 = −72.9 MW.
At 59.98 Hz its Reporting ACE of 10 MW is well inside that limit, which tightens as frequency falls: at 59.946 Hz it is −27 MW. A minute with less than half its frequency samples valid is dropped and restarts the 30-minute count.
Where BAL-002-3 and BAL-003-2 meet ACE
BAL-002-3 uses Reporting ACE as its recovery test. After a Reportable Balancing Contingency Event, the Balancing Authority or Reserve Sharing Group must bring Reporting ACE back within the Contingency Event Recovery Period, which the Glossary sets at 15 minutes. The target is zero if ACE was zero or positive just before the event, or its pre-event value if it was negative (R1, part 1.1). It must plan for Contingency Reserve at least equal to its Most Severe Single Contingency (R2), and restore it within 90 minutes after the recovery period (R3).
BAL-003-2 sets the B in the equation. For a Balancing Authority in a multiple-BA Interconnection that is not receiving Overlap Regulation Service, a fixed Frequency Bias Setting is the ERO-validated value, put into the ACE calculation within the ERO's implementation period (R2). A variable one must stay below zero at all times, and be equal to or more negative than the Frequency Response Obligation whenever frequency is more than 0.036 Hz from 60 Hz (R3).
What it is worth on the exam
Area Control Error is knowledge area 1.d, in Resource and Demand Balancing. All four content outlines list calculating and monitoring it among the operator's tasks.
| Exam | ACE (1.d) | ACE, Reserves, AGC and Frequency together | Scored questions |
|---|---|---|---|
| RC | 4 | 15 | 120 |
| BT | 4 | 17 | 120 |
| TO | 1 | 6 | 100 |
| BI | 4 | 19 | 100 |
Under PER-003-2, Balancing Authority positions accept the RC, BT or BI certificate, the three exams that carry 4 ACE questions (which certification you need). Try three free ACE questions. In the iPhone, iPad and Mac app, the AGC control board leaves the ACE for you to calculate.
A Balancing Authority's Reporting ACE has held near +150 MW for several minutes while Actual Frequency sits on the Scheduled Frequency of 60.00 Hz. Which action fits the condition?
- A. Request emergency assistance from an Adjacent Balancing Authority
- B. Reduce generation in its own Area until Reporting ACE nears zero
- C. Enter a 150 MW Interchange Meter Error to zero the display
- D. Ask the Reliability Coordinator to start a Time Error Correction
Show the answer
Answer B Reduce generation in its own Area until Reporting ACE nears zero
With Actual Frequency equal to Scheduled Frequency the Frequency Bias term is zero, so Reporting ACE is the interchange error alone: the Balancing Authority is delivering 150 MW more than it scheduled and is over-generating. A surplus needs no assistance from a neighbor, and Interchange Meter Error compensates only known metering or data errors, so entering one to hide a real control deficiency would falsify the calculation.
Reference: NERC Glossary - Reporting ACE, Frequency Bias Setting, Interchange Meter Error (IME)
From BAL-001-2, BAL-002-3 and BAL-003-2, the Glossary of Terms Used in NERC Reliability Standards and the four content outlines (June 2023). Standard status as shown on nerc.com on November 6, 2026.
Questions
Area Control Error FAQ
What is the difference between ACE and Reporting ACE?
ACE is the instantaneous interchange error, adjusted for Frequency Bias and meter error. Reporting ACE is its scan-rate values in MW, and it is the term the Glossary points to for compliance.
What sign does the Frequency Bias Setting have?
Negative, in MW/0.1 Hz. BAL-003-2 R3 requires a variable setting to stay below zero at all times.
How long can Reporting ACE stay beyond the BAAL?
Up to 30 consecutive clock-minutes. BAL-001-2 R2 is broken when the clock-minute average stays beyond the limit for longer than that.
Does BAL-001-2 apply to a Transmission Operator?
No. It applies to Balancing Authorities and Regulation Reserve Sharing Groups. The TO exam carries one scored ACE question.
Which version of BAL-001 is in force?
BAL-001-2, effective July 1, 2016. It was the only BAL-001 version listed as Mandatory Subject to Enforcement on nerc.com on November 6, 2026, apart from the ERCOT regional standard BAL-001-TRE-2.