Area Control Error (ACE)

1.d Area Control Error (ACE) is one of the 31 knowledge areas in the NERC System Operator Certification content outlines. It is worth 4 scored questions on RC, 4 on BT, 1 on TO and 4 on BI. On TO it is a single question. Grid Prep has 36 questions on it. In the bank, they most often cite BAL-005-1. 3 are free below.

Free sample: 3 of 36

Answer each one before you open the explanation. On the exam there's no explanation, and you have about 77 seconds a question on RC and BT, 90 on TO and BI.

Question 1 · Recall

In which Interconnection may a Balancing Authority include an Automatic Time Error Correction term in its Reporting ACE equation?

  1. A. the Western Interconnection
  2. B. the Eastern Interconnection
  3. C. the Quebec Interconnection
  4. D. the ERCOT Interconnection
Show the answer

Answer A the Western Interconnection

NERC's definition states that Automatic Time Error Correction applies only in the Western Interconnection. In any other Automatic Generation Control mode, and in the other three Interconnections, the term is zero.

Reference: NERC Glossary - Automatic Time Error Correction (ATEC)

Question 2 · Analysis

A Balancing Authority in a multiple Balancing Authority Interconnection keeps finding small errors in the scan rate data feeding Reporting ACE, and its operators are starting to distrust the displayed value. What does BAL-005-1 require it to have?

  1. A. a monthly error report to the Reliability Coordinator
  2. B. an immediate transfer to manual control until the errors clear
  3. C. an Operating Process to identify and mitigate the scan rate errors
  4. D. a backup Reporting ACE calculated from revenue meters
Show the answer

Answer C an Operating Process to identify and mitigate the scan rate errors

R6 requires a Balancing Authority inside a multiple Balancing Authority Interconnection to implement an Operating Process that identifies and mitigates errors affecting the accuracy of the scan rate data used in Reporting ACE. The other three may be sensible local practices, but none of them is what the standard obliges the Balancing Authority to have.

Reference: BAL-005-1 R6

Question 3 · Analysis

A Balancing Authority's Reporting ACE has held near +150 MW for several minutes while Actual Frequency sits on the Scheduled Frequency of 60.00 Hz. Which action fits the condition?

  1. A. Request emergency assistance from an Adjacent Balancing Authority
  2. B. Reduce generation in its own Area until Reporting ACE nears zero
  3. C. Enter a 150 MW Interchange Meter Error to zero the display
  4. D. Ask the Reliability Coordinator to start a Time Error Correction
Show the answer

Answer B Reduce generation in its own Area until Reporting ACE nears zero

With Actual Frequency equal to Scheduled Frequency the Frequency Bias term is zero, so Reporting ACE is the interchange error alone: the Balancing Authority is delivering 150 MW more than it scheduled and is over-generating. A surplus needs no assistance from a neighbor, and Interchange Meter Error compensates only known metering or data errors, so entering one to hide a real control deficiency would falsify the calculation.

Reference: NERC Glossary - Reporting ACE, Frequency Bias Setting, Interchange Meter Error (IME)

The full bank

The other 33 ACE questions

Full Access opens all 36 in this area as 12-question sets, least-seen first, plus the rest of the 1,224 and unlimited mock exams at exam pace. The Library card for 1.d holds the area's seven must-know numbers. To start free in the browser: 50 practice answers and a 30-question timed taster, split to your exam's weighting.