1.c · Resource and Demand Balancing · free sample

Automatic Generation Control (AGC)

1.c Automatic Generation Control (AGC) is one of the 31 knowledge areas in the NERC System Operator Certification content outlines. It is worth 3 scored questions on RC, 4 on BT, 1 on TO and 5 on BI. On BI that is the most any single area carries. On TO it is a single question. Grid Prep has 45 questions on it. In the bank, they most often cite BAL-005-1, BAL-001-2 and BAL-003-2. 3 are free below.

Free sample: 3 of 45

Answer each one before you open the explanation. On the exam there's no explanation, and you have about 77 seconds a question on RC and BT, 90 on TO and BI.

Question 1 · Recall

What minimum accuracy does BAL-005-1 demand of the frequency metering equipment used to calculate Reporting ACE?

  1. A. 0.0001 Hz
  2. B. 0.001 Hz
  3. C. 0.100 Hz
  4. D. 0.010 Hz
Show the answer

Answer B 0.001 Hz

Requirement R3 Part 3.2 sets the minimum accuracy at 0.001 Hz, and Part 3.1 sets a minimum availability of 99.95 percent for each calendar year. Coarser metering would corrupt the 10B frequency term in Reporting ACE.

Reference: BAL-005-1 R3 Part 3.2

Question 2 · Application

BAL-005-1 sets a minimum yearly availability for the system a Balancing Authority uses to calculate Reporting ACE. Across an 8,760-hour year, what is the longest total unavailability that still meets it?

  1. A. 87.6 hours
  2. B. 17.5 hours
  3. C. 4.4 hours
  4. D. 43.8 hours
Show the answer

Answer D 43.8 hours

Requirement R5 sets the minimum at 99.5 percent of each calendar year, and 0.5 percent of 8,760 hours is 43.8 hours. The 4.4-hour figure follows from the 99.95 percent availability R3 sets for frequency metering equipment, which is a separate requirement.

Reference: BAL-005-1 R5

Question 3 · Application

A generator sitting inside one Balancing Authority Area is carried as a Pseudo-Tie by a second Balancing Authority. Where does the Pseudo-Tie value land in that second Balancing Authority's Reporting ACE?

  1. A. In the frequency bias term, scaled by the Frequency Bias Setting
  2. B. In the Interchange Meter Error term, until the hour is settled
  3. C. In Actual Net Interchange, the same way a Tie Line does
  4. D. In Scheduled Net Interchange, the same way an Interchange Schedule does
Show the answer

Answer C In Actual Net Interchange, the same way a Tie Line does

The Glossary defines a Pseudo-Tie as a time-varying energy transfer updated in Real-time and included in the Actual Net Interchange term the same way a Tie Line is. A Dynamic Schedule is the counterpart that lands in Scheduled Net Interchange, which is why the two are so easily confused.

Reference: NERC Glossary - Pseudo-Tie, Dynamic Interchange Schedule

The full bank

The other 42 AGC questions

Full Access opens all 45 in this area as 12-question sets, least-seen first, plus the rest of the 1,224 and unlimited mock exams at exam pace. The Library card for 1.c holds the area's seven must-know numbers. To start free in the browser: 50 practice answers and a 30-question timed taster, split to your exam's weighting.